Arc flash PPE and electrical safety gear: arc rated clothing and kits, hoods and shields, insulating gloves, insulated tools, rain gear and accessories.
Showing all 182 products
Arc rated (AR) clothing and equipment carry an arc rating in cal/cm². Under NFPA 70E, the Standard for Electrical Safety in the Workplace, an arc flash risk assessment sets the incident energy or the PPE category for each task, and the arc rating of the clothing should meet or exceed it. OSHA’s 29 CFR 1910.335 requires electrical protective equipment suited to the body part and the work, nonconductive head protection where there is a danger of head injury from shock or burns, and eye or face protection wherever electric arcs or flashes could cause injury.
When the PPE category method is used, NFPA 70E sets a minimum arc rating for the clothing in each category:
The 11 and 12 cal kits here exceed the Category 2 minimum, and the 40 cal kits meet the Category 4 minimum. Each category also calls for a hard hat, safety glasses or goggles, hearing protection and gloves, and Category 2 pairs an arc rated face shield with an arc rated balaclava unless an arc flash suit hood is worn.
OSHA 1910.137 sets a maximum use voltage for each glove class: 500 V for Class 00, 1,000 V for Class 0, 7,500 V for Class 1 and 17,000 V for Class 2, all AC. Gloves must be inspected and air tested before each day’s use and worn with leather protectors over them except in limited cases. They must be electrically tested before first issue and every 6 months, and insulating blankets before first issue and every 12 months.
Use the incident energy or PPE category from your arc flash risk assessment or equipment label, and choose clothing with an arc rating at or above it. Under the NFPA 70E PPE category method, the minimum arc ratings are 4 cal/cm² for Category 1, 8 for Category 2, 25 for Category 3 and 40 for Category 4.
The clothing's arc rating exceeds the 8 cal/cm² minimum for Category 2. NFPA 70E's Category 2 list also includes an arc rated face shield with an arc rated balaclava, or an arc flash suit hood, plus a hard hat, safety glasses or goggles, hearing protection, gloves and leather footwear, so add any items the kit does not include.
Each class has a maximum use voltage (AC) under OSHA 1910.137: Class 00, 500 V; Class 0, 1,000 V; Class 1, 7,500 V; Class 2, 17,000 V; Class 3, 26,500 V; Class 4, 36,000 V. This category stocks Class 00 to Class 2 gloves and glove kits.
OSHA 1910.137 requires rubber insulating gloves to be electrically tested before first issue and every 6 months after that, whenever their insulating value is suspect, after repair and after use without protectors. Inspect and air test gloves before each day's use. Odiz offers electrical glove testing.
In most cases, yes. OSHA 1910.137 requires protector gloves over insulating gloves, with limited exceptions, mainly for Class 00 and Class 0 gloves where small parts work needs unusually high finger dexterity. Gloves used without protectors must be tested before they are used again.
Yes. 40 cal Lite, Economy and Ultra Comfort hoods and shrouds are available on their own, with a hard hat, with a fan unit for airflow, with a light or headlamp, or with both a fan and a light.